COPPER WIRE AMPACITY
National Electric Code
[printer version]

Allowable Ampacities of Insulated Conductors Rated 0 through 2000 Volts, 60° to 90° C (140° to 194° F) Not More Than Three Current-Carrying Conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30° C (86° F).

Size

Temperature Rating of Conductor.  See Table 310-13

 

60°
(140° F)

75°
(167° F)

90°
(194° F)

AWG
kcmil

TYPES
TW±, UF±

TYPES
FEPW±
RH±, RHW±
THHW±, THW±
THWN±, XHHW±
USE±, ZW±

TYPES
TBS, SA, SIS, FEP±
FEPB±, RHH±
RHW-2, THHN±
THHW±

                      COPPER

18
16
14
12
10
8



20±
25±
30
40



20±
25±
35
50

14
18
25±
30±
40±
55

6
4
3
2
1

55
70
85
95
110

65
85
100
115
130

75
95
110
130
150

1/0
2/0
3/0
4/0
250
300
350
400
500

125
145
165
195
215
240
260
280
320

150
175
200
230
255
285
310
335
380

170
195
225
260
290
320
350
380
430

600
700
750
800
900

355
385
400
410
435

420
460
475
490
520

475
520
535
555
585

1000
1250
1500
1750
2000

455
495
520
545
560

545
590
625
650
665

615
665
705
735
750

CORRECTION FACTORS

Ambient Temp. C

For ambient temperatures other than 30° C (86° F), multiply he allowable ampacities shown above by the appropriate factor shown below.

21-25
26-30
31-35
36-40
41-45
46-50
51-55
56-60
61-70
71-80

1.08
1.00
.91
.82
.71
.58
.41

1.05
1.00
.94
.88
.82
.75
.67
.58
.33

1.04
1.00
.96
.91
.87
.76
.71
.58
.41

± Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelisk (±) shall not exceed 15 amperes for No. 14-20 amperes for No. 12 and 30 amperes for No. 10: or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.

Ref. NEC Table 310-16


ALUMINUM WIRE AMPACITY

National Electric Code
[printer version]

Allowable Ampacities of Insulated Conductors Rated 0 through 2000 Volts, 60° to 90° C (140° to 194° F) Not More Than Three Current-Carrying Conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30° C (86° F).

Size

Temperature Rating of Conductor.  See Table 310-13

60°
(140° F)

75°
(167° F)

90°
(194° F)

 

TYPES
TW±, UF±

TYPES
RH±, RHW±,
THHW±, XHHW±
USE±

THW±
THWN±

TYPES
TBS, SA, SIS,
THHN±, THHW±
THW2, THWN-2
RHH±, RHW-2,
USE-2,
XHH, XHHW
XHHW-2, ZW-2

AWG
kcmil

ALUMINUM OR COPPER-CLAD ALUMINUM

...
...
...
20±
25
30

...
...
...
20±
30±
40

...
...
...
25±
35±
45

...
...
...
12
10
8

40
55
65
75
85

50
65
75
90
100

60
75
85
100
115

6
4
3
2
1

100
115
130
150
170
190
210
225
260

120
135
155
180
205
230
250
270
310

135
150
175
205
230
255
380
305
350

1/0
2/0
3/0
4/0
250
300
350
400
500

285
310
320
330
355

340
375
385
395
425

385
420
435
450
480

600
700
750
800
900

375
405
435
455
470

445
485
520
545
560

500
545
585
615
630

1000
1250
1500
1750
2000

CORRECTION FACTORS

Ambient Temp. C

For ambient temperatures other than 30° C (86° F), multiply he allowable ampacities shown above by the appropriate factor shown below.

70-77
78-86
87-95
96-104
105-113
114-122
123-131
132-140
141-158
159-176

1.08
1.00
.91
.82
.71
.58
.41
...
...
...

1.05
1.00
.94
.88
.82
.75
.67
.58
.33
...

1.04
1.00
.96
.91
.87
.82
.76
.71
.58
.41

± Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelisk (±) shall not exceed 15 amperes for No. 14-20 amperes for No. 12 and 30 amperes for No. 10: or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.

Ref. NEC Table 310-16

 